Schematics
42
5) HVAC setback
This type of temperature control system uses the relay labels « Heat », « Cool » and « Fan ».
Heat This relay is closed to control the temperature in economy mode
Cool This relay is closed to control the cooling
Fan This relay is closed during the cooling control process
In setback mode (economy)
When the ambient temperature is lower than the set point, the « Heat »relay is closed.
In normal mode (comfort)
The « Heat » relay is always closed, the temperature control is monitored by the thermostat
*.
In all modes
When the ambient temperature is higher than the cooling set point, the « Cool » relay is activated.
Connection schematic HVAC setback